(1) Structure:
- Lightweight frame: bolted anodised aluminium profiles with sealing strips for the cold-room section, and a steel frame for the condensing-unit section.
(2) The machine consists of:
- A low-temperature semi-hermetic CO2 compressor, approximately 2 kW, fitted with a variable frequency drive operating from 30 to 70 Hz.
- Two medium-temperature semi-hermetic CO2 compressors, approximately 8 kW, fitted with a variable frequency drive operating from 30 to 70 Hz.
- All equipment required by the regulations (dual safety valves, relief valve) and for CO2 use is included, along with CO2-specific servicing and maintenance tools.
- A fully equipped industrial low-temperature cold room.
- A 2.6 kW CO2 evaporator matched to the low-temperature compressor, fitted with an electronic expansion valve.
- A variable heat load matched to the evaporator capacity.
- A fully equipped industrial medium-temperature cold room.
- An 8.1 kW CO2 evaporator matched to the medium-temperature compressor, fitted with an electronic expansion valve.
- An air-cooled gas cooler integrated into the frame.
- Oil separator, reservoir and oil return with electronic level control.
- A system that starts the medium-temperature compressor during prolonged shutdowns when power is available but no refrigeration is being produced.
- An independent safety unit that controls liquid receiver pressure during servicing when no electrical power is available.
- Safety valves all connected to a common manifold at the bottom, with provision for discharge outdoors.
- An electronic high-pressure control valve
for the receiver
- A liquid line with a replaceable-cartridge filter-drier and the valves needed for replacement, a liquid sight glass, relief valves and a heat exchanger for enhanced subcooling.
- A CO2 gas detector
- All pipework complies with the standards for CO2 use: K65 copper-iron (CuFe) tubing.
(3) Instrumentation:
- 16 temperature sensors on the cooling circuit with analogue output
- 6 temperature sensors on air at exchangers with analogue output
- 4 pressure sensors on the cooling circuit with analogue output
- An electrical power analyser measuring voltage, current, phase shift and the various electrical power quantities.
- A system schematic on a touchscreen, with LEDs showing which electrical devices are operating.
(4) The electrical part includes:
- An electrical supply box
- Standard safety components (main isolator, residual-current circuit breaker, earth connection and white indicator light).
- A thermal-magnetic circuit breaker for each component.
- Signal lights for each element
- Measurements displayed on a 10-inch touchscreen, including a system schematic and real-time graphs.
- The data acquisition system can connect to a PC locally via Ethernet or Wi-Fi, or remotely via the internet. All data can be retrieved in an Excel-compatible file.