Steam boiler: Steam flow : 250kg/h Working pressure : 9 bars Burner feeding :Natural  gas or fuel (on demand) Working mode : permanent presence The boiler come with : -pressure manometer -two level glass sights -safety valve -draining valve -check valve and feeding valve on the water circuit -electric cabinet with audible alarm -water level controller -pressure controller  Utilities skid : It comes with : -electric cabinet supplying power to all the elements -water feeding line with a water meter, a backflow preventer, a filter, a manometer, a pressure reducer and all necessary -a volumetric softener with salt tank -some valves for samples -water tank (250L) made of stainless steel with lateral level sight -a dosing pump  Steam supply : It comes with:  Steam feeding : -it is connected to the boiler outlet -it includes a water separator -it includes a Y filter -it includes a vortex flow meter (steam flow) -it includes pressure and temperature measurements -condensates are pumped back to the water tank 									     								      
								 | 
																	
								     
 Reducing valves: -the line allows to test two different reducing valves -each reducing valve has a stop valve before and after and a Y shaped filter -two different technologies are used (pilot operated pressure reducing valve and direct acting reducing valve) -a third line with a valve allows to bypass reducing valves   Control valves : -the line allows to test two different control valves -valves control the steam flow, depending from the water temperature at the outlet of the exchanger - each control valve has a stop valve before and after and a Y shaped filter -there is an electric actuator and a mechanical actuator -a third line with a valve allows to bypass control valves   Steam condenser : -the exchanger is tubular type and is cooled with water -the cooling power is designed to fit with the maximal steam flow generated by the boiler (about 130KW) -it is equipped with temperature sensors on the different circuits -it is equipped with a water flowmeter -it includes a vacuum breaker to avoid degradation when the steam condensates -condensates go to steam traps   Steam traps : -the line includes five steam traps -each steam trap consists in a different technologie (thermodynamic, inverted bucket, bimetallic, ball float and balanced pressure) -each steam trap is equipped with a sight glass and stop valve -condensates go back to the water tank   Water cooling circuit : -Cooling unit outside -the cooling circuit includes a centrifugal pump -Cooling unit : -Average power : 140KW -local electric cabinet with emergency stop -fans are controlled by a temperature switch -the structure is corrosion resistant -fans are protected -stop valves on the outlet and inlet -drain valve   Others characteristics : -the equipment include a pump (operated by steam) for condensate return -the equipment also include a blowdown tank. -the equipment will be fitted to laboratory 								 |