The bench is installed on an aluminum profile structure equipped with four directional brake castors.
It includes an electrical box with main power disconnector and 30mA differential circuit breaker.
1. Thermodynamic water heaters
Capacity: 200L
Total electrical power consumption: 1800W
COP (air at 7°C): 3.18
Duration of T°: 7h41
Refrigerant: R290
Ergonomic lifestyle adjustment (Manual or Eco+, Boost, Away functions)
- Monitoring energy consumption (on the product or via the application)
- Eco+ mode and Away mode to adapt to hot water needs
- Boost function to increase hot water production in case of unforeseen events 
- Visualization and adjustment of the water quantity in the event of unforeseen events and visualization of consumption 
- Cep Gain: Interface shutdown after 30 seconds.
- Intuitive digital interface
- Acoustic comfort: 47 dB(A)
2. Backup electric resistance
Power: 1800W
3.Evacuation of condensates
 
4. Low pressure sensor
5. High pressure sensor
6. Safety group with evacuation downwardly in case of overpressure and valve on feed
7. Quick connector sealing (connection towards the ECS100 bench)
Integrated instrumentation:
-low pressure sensor
-High pressure sensor
-thermocouple temperature T (X10): -20 to + 100 ° C
-Electrical network analyzer (voltage, current, power, frequency, cos Phy)
The measurements are displayed on a 7 "touchscreen: